Modular frequency-conversion design ensures energy-efficient and stable operation, delivering optimized energy savings and high-output performance across industrial, agricultural, and commercial facilities.
Model | Unit | MC065 EA4DLH3 | |
Rated heating capacity | kW | 65 | |
Rated Heating Input Power | kW | 18 | |
Rated Heating COPh | – | 3.61 | |
Nominal Heating Capacity | kW | 45 | |
Nominal Heating Input Power | kW | 17.6 | |
Nominal Heating COPh | – | 2.56 | |
Nominal Cooling Capacity | kW | 62 | |
Nominal Cooling Input Power | kW | 19.1 | |
Nominal Cooling COPc | 一 | 3.25 | |
IPLV(C) | – | 4.55 | |
IPLV(H) | – | 3.32 | |
Maximum Input Power | kW | 27.8 | |
Maximum Input Current | A | 46.9 | |
Power Supply | 一 | 380V/3N-/50Hz | |
Cooling Operating Ambient Temperature Range | ℃ | 10-48 | |
Heating Operating Ambient Temperature Range | ℃ | -35~40 | |
Compressor | Type | 一 | DC Inverter Rotary Compressor |
Quantity | – | 2 | |
Fan | Type | – | DC Inverter Axial Fan |
Quantity | – | 4 | |
Rated Power | kw/unit | 0.17 | |
Water-Side Heat Exchanger | Type | 一 | Plate Heat Exchanger |
Water flow | m/h | 10.7 | |
Unit Water Pressure Drop | kPa | 31 | |
Unit Inlet/Outlet Pipe Connection Size | – | Rc2 | |
Design Maximum Inlet/Outlet Water Temperature Difference | C | 7 | |
Dimensions (L×W×H) | mm | 1700×780×2160 | |
Unit Operating Weight | kg | 415 | |
Unit Gross Weight | kg | 410 |