Featuring a top-exhaust design that optimizes confined spaces for minimal footprint, enhancing energy efficiency.
Model | Unit | MC040EB | |
Rated heating capacity | kW | 44 | |
Rated Heating Input Power | kW | 13.70 | |
Rated Heating COPh | 一 | 3.21 | |
Nominal Heating Capacity | kW | 29 | |
Nominal Heating Input Power | kW | 12.34 | |
Nominal Heating COPh | – | 2.35 | |
Low-Temperature Heating Capacity | kW | 23.5 | |
Low-Temperature Heating Input Power | kW | 11.52 | |
Low-Temperature Heating COPdh | – | 2.04 | |
Nominal Cooling Capacity | kW | 40 | |
Nominal Cooling Input Power | kW | 14.1 | |
Nominal Cooling COPc | – | 2.84 | |
IPLV(C) | 一 | 4.30 | |
IPLV(H) | – | 3.05 | |
Rated HSPF | – | 2.90 | |
Rated APF | – | 2.84 | |
Maximum Input Power | A | 19.7 | |
Maximum Input Current | A | 33.5 | |
Power Supply | – | 380V/3N~/50Hz | |
Cooling Operating Ambient Temperature Range | ℃ | 10~48 | |
Heating Operating Ambient Temperature Range | ℃ | -35-40 | |
Compressor | Type | – | DC Inverter Scroll Compressor |
Quantity | – | 1 | |
Fan Motor | Type | – | DC Inverter Axial Fan |
Quantity | – | 1 | |
Rated output power | kw/unit | 0.92 | |
Rated Power | Inverter Water Pump | kW | 一 |
Fixed-Speed Water Pump | kW | 一 | |
Water-Side Heat Exchanger | Type | – | Plate Heat Exchanger |
Water flow | m3/h | 6.9 | |
Unit Water Pressure Drop | kPa | 44 | |
Unit External Head | Inverter Water Pump | m | 一 |
Fixed-Speed Water Pump | m | 一 | |
Unit Inlet/Outlet Pipe Connection Size | – | Rc1 1/4 | |
Design Maximum Inlet/Outlet Water Temperature Difference | ℃ | 7 | |
Dimensions (L×W×H) | mm | 1080x840x1670 | |
Unit Operating Weight | kg | 250 | |
Unit Gross Weight | kg | 246 |