40 KW Residential Heat Pump

Featuring a top-exhaust design that optimizes confined spaces for minimal footprint, enhancing energy efficiency.

Model Unit MC040EB
Rated heating capacity kW 44 
Rated Heating Input Power kW 13.70 
Rated Heating COPh 一 3.21 
Nominal Heating Capacity kW 29 
Nominal Heating Input Power kW 12.34 
Nominal Heating COPh – 2.35 
Low-Temperature Heating Capacity kW 23.5 
Low-Temperature Heating Input Power kW 11.52 
Low-Temperature Heating COPdh – 2.04 
Nominal Cooling Capacity kW 40 
Nominal Cooling Input Power kW 14.1 
Nominal Cooling COPc – 2.84 
IPLV(C) 一 4.30 
IPLV(H) – 3.05 
Rated HSPF – 2.90 
Rated APF – 2.84 
Maximum Input Power A 19.7 
Maximum Input Current A 33.5 
Power Supply – 380V/3N~/50Hz
Cooling Operating Ambient Temperature Range ℃ 10~48
Heating Operating Ambient Temperature Range ℃ -35-40
Compressor Type – DC Inverter Scroll Compressor
Quantity – 1 
Fan Motor Type – DC Inverter Axial Fan
Quantity – 1 
Rated output power kw/unit 0.92 
Rated Power Inverter Water Pump kW 一
Fixed-Speed Water Pump kW 一
Water-Side Heat Exchanger Type – Plate Heat Exchanger
Water flow m3/h 6.9 
Unit Water Pressure Drop kPa 44 
Unit External Head Inverter Water Pump m 一
Fixed-Speed Water Pump m 一
Unit Inlet/Outlet Pipe Connection Size –    Rc1 1/4
Design Maximum Inlet/Outlet Water Temperature Difference ℃ 7 
Dimensions (L×W×H) mm 1080x840x1670
Unit Operating Weight kg 250 
Unit Gross Weight  kg 246